PROFINET IO (PN-IO)
The PROFINET I/O (PN-IO) protocol is a field bus protocol for decentralized I/O.
PROFINET/IO is based on connectionless DCE/RPC and the "lightweight" PROFINET/RT (ethernet type 0x8892) protocols:
-
The context manager (CM) part handles context information (such as establishment) and uses connectionless DCE/RPC as its underlying protocol.
-
The actual cyclic data transfer and acyclic notification uses the "lightweight" PROFINET/RT protocol.
-
There are other related PROFINET protocols, such as PROFINET/DCP, which handles addressing.
History
XXX - add a brief description of PN-IO history
Protocol dependencies
-
DCE/RPC: PN-IO uses connectionless DCE/RPC as its transport protocol.
-
PROFINET/RT: PN-IO uses PROFINET/RT for the actual user data transfer.
Example traffic
Frame 23 (64 bytes on wire, 64 bytes captured)
Arrival Time: Mar 16, 2006 21:08:09.415475000
Time delta from previous packet: 0.126966000 seconds
Time since reference or first frame: 9.698024000 seconds
Frame Number: 23
Packet Length: 64 bytes
Capture Length: 64 bytes
Protocols in frame: eth:vlan:pn_rt:pn_io
Ethernet II, Src: 192.168.0.100 (08:00:06:6b:a5:2d), Dst: 192.168.0.101 (08:00:06:6b:f9:81)
Destination: 192.168.0.101 (08:00:06:6b:f9:81)
Source: 192.168.0.100 (08:00:06:6b:a5:2d)
Type: 802.1Q Virtual LAN (0x8100)
802.1Q Virtual LAN
110. .... .... .... = Priority: 6
...0 .... .... .... = CFI: 0
.... 0000 0000 0000 = ID: 0
Type: PROFInet (0x8892)
PROFINET cyclic Real-Time, RTC1, ID:0xc000, Len: 40, Cycle:16384 (Valid,Primary,Ok,Stop)
FrameID: 0xc000 (0xC000-0xFAFF: Real-Time(class=1): Cyclic)
CycleCounter: 16384
DataStatus: 0x25 (Frame: Valid and Primary, Provider: Ok and Stop)
00.. .... = Reserved (should be zero): 0x00
..1. .... = StationProblemIndicator (1:Ok/0:Problem): 0x01
...0 .... = ProviderState (1:Run/0:Stop): 0x00
.... 0... = Reserved (should be zero): 0x00
.... .1.. = DataValid (1:Valid/0:Invalid): 0x01
.... ..0. = Reserved (should be zero): 0x00
.... ...1 = State (1:Primary/0:Backup): 0x01
TransferStatus: 0x00 (OK)
PROFINET IO Cyclic Service Data Unit: 40 bytes
IOxS: 0x00 (bad)
.... ...0 = Extension (1:another IOxS follows/0:no IOxS follows): 0x00
...0 000. = Reserved (should be zero): 0x00
.00. .... = Instance (only valid, if DataState is bad): detected by subslot (0x00)
0... .... = DataState (1:good/0:bad): 0x00
Data: 39 bytes (including GAP and RTCPadding)
0000 08 00 06 6b f9 81 08 00 06 6b a5 2d 81 00 c0 00 ...k.....k.-....
0010 88 92 c0 00 00 00 00 00 00 00 00 00 00 00 00 00 ................
0020 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 ................
0030 00 00 00 00 00 00 00 00 00 00 00 00 40 00 25 00 ............@.%.Wireshark
The PN-IO dissector is fully functional.
Preference Settings
There are no PN-IO specific preference settings.
Example capture file
XXX - Add a simple example capture file to the SampleCaptures page and link from here. Keep it short, it's also a good idea to gzip it to make it even smaller, as Wireshark can open gzipped files automatically.
Display Filter
A complete list of PN-IO display filter fields can be found in the display filter reference
-
Show only the PN-IO based traffic:
pn_io -
Show the PN-IO based traffic without the cyclic PN-IO telegrams (to avoid a lot of "noise"):
pn_io && !pn_io.ioxs